Omni Hotel - Houston, TX.
Type of Equipment: 2-350 ton York Centrifugal Chillers #MTG-95 (Lead & Lag) 1-75 ton York Reciprocating Chiller #YCWZ99RP-46 (Back up)
Install Date: Aug 10,1999
Results:
Lead and Lag chillers had significant reductions Including: Chilled LQD supply tempdown 2°f & 11°F, Chilled H2O return temp 4° & 14° F, condenser Supply temp 6°F & 4°F. KWH demand was recuced by 32.14% & 17.65%. Back up: reduced Chilled H2O supply temp 2°F, chilled H2O supply temp 6°F, condenser supply temp 4°F, condenser return temp 4°F.Reduced KWH demand 6.3%
Verified: Juan Ruiz of Omni. Projected overall utility savings of 15%



Rockwell International - Duluth, GA.
Type of Equipment: 1-500 ton Carrier Centrifugal Process Chiller #19DM-7850CQ
Install Date: 9/22/1999
Results:
11.3% reduction in run time. Kwh demand reduced 10%. Plant Manager reported in May 1992 & July 1996 that Chiller was running superbly. He also reported manufacturers reps were impressed with condition of equipment at a visual inspection.
Verified:
Plant personnel at Rockwell


Metro Nashville Airport - Nashville, TN.
Type of Equipment: 3-100 ton Trane Centrivac Chillers (R-11 Refrigerant)
Install Date: 02/01/1997
Results:
Total utility bill reduced aveage of 7% over 5 months of test.
Verified: Results based on utiliity bill, was not separately monitored.



California State Polytech University Building #3 - Pomona, CA.
Type of Equipment: 1-215 ton Trane Centrivac Chiller
Install Date: 7/6/1998
Results:
KWH demand reduced by 28% with chiller operating at an average of 70% load and no week end operation.
Verified:
University personnel


Western Lithograph, Inc. - Houston, TX.
Type of Equipment: 100 ton Carrier Flowtronic Chiller(Lead) & 70 ton Carrier Flowtronic Chiller(Lag)
Install Date: 1999
Results:
KWH demand reduced by 28.5%. Projected annual savings of $11,275.
Verified:
Test was conducted by Thermonomics


Casino Rouge (River Boat) - Baton Rouge, LA.
Type of Equipment: 1-220 ton York Reciprocating Chiller
Install Date: 1999
Results:
KWH demand reduced by 37.19% Projected savings of $15,184.
Verified: Electro-Test, Inc. Baton Rouge, LA.




Casino Rouge (Landside) - Baton Rouge, LA.
Type of Equipment: 2-200 ton Trane Screw Chillers
Install Date: 1999
Results:
KWH demand reduced by 17.3%. Projected savings of$43,620.
Verified: Electro-Test, Inc. Baton Rouge, LA.



Friskies Pet Care plant Unit #3 - St. Joseph, MO.
Type of Equipment: 1-100 ton Vilter Compressor (Ammonia) #12R45810
Install Date: 8/1/1996
Results:
KWH reduced by 28%
Verified: Gene Watts St. Joseph, MO.



Rosenthal Meat Science Technology Center - Texas A&M University.
Type of Equipment: 1-100 ton Vilter Compressor (Ammonia) #12R45810
Install Date: 6/5/1989
Results:
KWH reduced by 14.7%. 277% more oil returned than added.
Verified: Not Available



Gaylers Store Facility - Clearwater, FL.
Type of Equipment: 1-210 ton Trane #PCV-2C-C1DI
Install Date: Dec, 1988
Results:
15.83% utility bill savings. Run time decreased by 12.1% even though store increased it's hours after injection by 10%
Verified: Roger A. Henry, V.P. Construction and Real Estate, Mercantile Stover Co., Inc. Columbia SC.


Reid Plastics, Inc. - City of Industry, CA.
Type of Equipment: 210 ton Carrier Chiller (7-30 ton compressors)
Install Date: 6/16/1998
Results:
KWH demand reduced by 21%, water supply temp reduced by 3°F
Verified: Reid Plastic personnel


Federal owned Bldg. - Washington DC.
Type of Equipment: 1-100 ton Trane Centri-Vac Chiller #N4A0050193
Install Date: 11/19/1997
Results:
KWH demand reduced by 20%
Verified: Sta-Cool Inc.

Average Savings Of 20.07% (Not including Ammonia units)